The Air Shower Room should not be located at the high speed dust source and vibration source. Do not use volatile oil, thinner, corrosive solvents, etc. to wipe the box, so as not to hurt the paint layer or cause discolouration.
The following places should not be used: Low temperature, high temperature, humidity, condensation, dust and fumes, mist places.
Generally according to the number of people in the workshop to determine the length of the Air Shower, for example, the workshop has about 20 people, you can choose to use each time through 1 person, so that more than 20 people can pass in about 10 minutes. Workshop 50 people, you can choose a pass 2-3 people each time, workshop 100 people, you can choose a pass 6-7 people each time, if the workshop in 200 people, you can choose the corridor air shower, that is to say, people go directly from the inside, do not have to stay, can greatly save time.
After connecting the power supply, the double doors will be interlocked immediately, you can only open one of the doors, you can't force open two doors at the same time, otherwise it will damage the double door interlocking system. Enter the Air Shower Room from the entrance door, after closing the entrance door, the blowing shower will start immediately. After the blowing shower is finished, the entrance door is locked, you can only open the exit door and walk out from the exit door, at this time you can't push open the entrance door forcibly, otherwise it will damage the double door interlocking system.
Maintenance of the Air Shower Room, according to the actual use of the situation to determine a frequency for cleaning. For example, for the pre-filter, can be washed with water or vacuum dust washing and other ways to clean, normal three months replacement, the main filter, then, every year to test 2 to 4 times, clean room according to the value of the wind speed or pressure measurement to decide whether the device should be changed. Specifically include:
1. According to the actual use of the situation, regularly remove the filter media in the primary air filter cleaning.
2. When the wind speed is found to be small, the surface of the primary air filter should be checked firstly to see if it is black, if it is black, it means that the pre-filter is more dusty and the resistance is increased, which means that the non-woven fabric in the primary air filter should be removed and cleaned or replaced.
3. When the non-woven cloth can not be replaced or cleaned to improve the wind speed, it means that the high-efficiency air filter has been clogged, resulting in increased resistance, then the high-efficiency air filter should be replaced.
4. When replacing the high-efficiency air filter, it is necessary to remove the spray ball plate, remove the high-efficiency filter, and replace the new high-efficiency air filter according to the specifications of the original high-efficiency filter. When installing the HEPA filter, make sure the arrow mark on the HEPA filter points to the direction of airflow. And make sure the seal is good to prevent leakage.
5. After the replacement of the high-efficiency filter, make sure that there is no leakage on the frame and use the dust particle counter to test it properly, and it can work normally only after it reaches the technical indexes.
6. Regularly overhaul the electrical line, if there is any fault, you can refer to the electrical schematic diagram for maintenance.
7. Regular maintenance of the door, so that the electronic lock and its lock hole alignment, so as not to lock the pin jammed.